Can the EcoFlow Delta Pro 3 Run a ResMed AirSense 11 CPAP (With Heated Humidifier & Tube)?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the EcoFlow Delta Pro 3 (4,096 Wh) paired with the ResMed AirSense 11 CPAP (With Heated Humidifier & Tube).

Configure your system

800 W
25 ft (7.6 m)
100%
Source outlets
NEMA L14-30R / NEMA 6-20R / TT-30R
Load connection
NEMA 5-15P
Verified Hardware Match

Check current bundle pricing for the EcoFlow Delta Pro 3 plus a transfer switch kit for this setup.

As an Amazon Associate, we earn from qualifying purchases.

Verified Compatible

EcoFlow Delta Pro 3 handles 65 W continuous and 90 W surge with headroom.

3,935 W of continuous capacity left for other circuits.

Continuous load
2%
Runtime (no sun)
53.6 hrs
100% duty · 85% inverter eff.
Solar recharge
6.4 hrs
1.4 sun-days at 800 W
Min. copper wire
14 AWG
0.1% drop @ 25 ft
Overcurrent device
15A Breaker
0.5A load × 1.25 = 0.7A
Live schematic & breaker sizing diagram 120V AC • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER EcoFlow Delta Pro 3 4,096 Wh • 4,000 W 8,000 W surge • 120/240V 2% load 15A OCPD 14 AWG Cu 0.5A @ 120V CONNECTED LOAD ResMed AirSense 11 CPAP (With Heated Hum… 65 W running 90 W surge 120V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a ResMed AirSense 11 CPAP (With Heated Humidifier & Tube) on the EcoFlow Delta Pro 3

US/NA: Verified Compatible UK/EU/AU: Verified Compatible 2% inverter utilization

When pairing the EcoFlow Delta Pro 3 (4,096 Wh LiFePO4 capacity, 4,000 W continuous, 8,000 W surge) with a ResMed AirSense 11 CPAP (With Heated Humidifier & Tube) (65 W running, 90 W starting surge), the system operates at 2% of continuous inverter capacity on a 120 V North American circuit and 2% on a 230 V UK/EU/AU circuit. At a 100% duty cycle and 85% inverter efficiency, a full battery delivers roughly 53.6 hrs of off-grid runtime. Wiring the connection over a 25 ft run calls for a 15 A breaker and 14 AWG copper, terminated at a NEMA 5-15P connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the ResMed AirSense 11 CPAP (With Heated Humidifier & Tube) loads the EcoFlow Delta Pro 3's inverter to 2% of its 4,000 W continuous rating and 1% of its 8,000 W surge rating. Both figures are under the 80% sustained-load guideline, so this is a comfortable, verified match with 3,935 W of spare capacity for lights, a router or a refrigerator on the same unit.

CheckLoad requiresEcoFlow Delta Pro 3 providesUS/NAUK/EU/AU
Continuous output 65 W 4,000 W Pass Pass
Start-up surge 90 W 8,000 W Pass Pass
Voltage 120 V / 230 V 120/240 V / 230 V Pass Pass
Connection NEMA 5-15P NEMA L14-30R / NEMA 6-20R / TT-30R UK/EU/AU: BS 1363 13A / Schuko CEE 7/4 / AS/NZS 3112 10A

Critical loads value uptime over raw power. At 65 W, this equipment is small relative to the EcoFlow Delta Pro 3's 4,000 W inverter, so the deciding factors are runtime, pure-sine output quality and switchover time. Most modern power stations offer UPS or EPS pass-through with a 10–30 ms transfer, which is fast enough for CPAP machines, routers and servers with active-PFC power supplies. For medical devices, always confirm with the device manufacturer and keep a secondary backup plan; for CPAP specifically, a DC adapter can extend runtime by 20–30% by skipping inverter losses.

As a portable power station, the EcoFlow Delta Pro 3 integrates the LiFePO4 battery, inverter, MPPT solar controller and AC outlets in one chassis, so it can be wheeled to the load or connected to a transfer switch through its NEMA L14-30R / NEMA 6-20R / TT-30R outlet.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 4,096 Wh rating to about 3,482 Wh of deliverable AC energy (85% system efficiency). Duty cycle is the share of each hour the load actually draws its running power — thermostats, pressure switches and intermittent use all lower it.

Runtime (h) = (4,096 Wh × 0.85) ÷ (65 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 16 W 8.9 days 0.4 kWh
50% 33 W 4.5 days 0.8 kWh
65% 42 W 3.4 days 1.0 kWh
100% 65 W 53.6 hrs 1.6 kWh

At a 50% duty cycle the EcoFlow Delta Pro 3 covers a full day (4.5 days) without any recharge — ample for a typical overnight outage.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 65 W ÷ 120 V = 0.5 A, × 1.25 = 0.7 A, which rounds up to the next standard NEC 240.6 size of 15 A. The conductor must be protected by that breaker (75 °C ampacity at least 15 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (65 W ÷ 120 V) × 1.25 = 0.7 A → 15 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 15 A 14 AWG 0.07% Sized by ampacity
50 ft (15.2 m) 15 A 14 AWG 0.14% Sized by ampacity
75 ft (22.9 m) 15 A 14 AWG 0.21% Sized by ampacity
100 ft (30.5 m) 15 A 14 AWG 0.28% Sized by ampacity

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 0.3 A, so a 6 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 6 A 1.5 mm² 0.02%
15 m (49 ft) 6 A 1.5 mm² 0.04%
22.5 m (74 ft) 6 A 1.5 mm² 0.07%
30 m (98 ft) 6 A 1.5 mm² 0.09%

Because the current is modest, 14 AWG copper stays within the voltage-drop target all the way to 100 ft.

4. Solar Array Recharge Time Breakdown

The EcoFlow Delta Pro 3 accepts up to 2,600 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 12.8 hrs 2.8 +288 W
800 W 640 W 6.4 hrs 1.4 +608 W
1,600 W 1,280 W 3.2 hrs 0.7 +1,248 W
2,600 W 2,080 W 2.0 hrs 0.4 +2,048 W

A typical 800 W portable array refills the battery in about 6.4 hrs of strong sun, while maxing out the 2,600 W input cuts that to 2.0 hrs. To fully offset the ResMed AirSense 11 CPAP (With Heated Humidifier & Tube) at a 50% duty cycle (33 W average) during daylight you need roughly 50 W of panels, which this unit can accept.

5. Frequently Asked Questions

Can the EcoFlow Delta Pro 3 run a ResMed AirSense 11 CPAP (With Heated Humidifier & Tube)?

Yes. The EcoFlow Delta Pro 3 delivers 4,000 W continuous and 8,000 W surge, covering the ResMed AirSense 11 CPAP (With Heated Humidifier & Tube)'s 65 W running and 90 W start-up draw at 2% inverter utilization.

How long will the EcoFlow Delta Pro 3 run a ResMed AirSense 11 CPAP (With Heated Humidifier & Tube)?

With 4,096 Wh of capacity and 85% inverter efficiency, expect about 53.6 hrs of continuous operation and 4.5 days at a 50% duty cycle. Adding solar input during the day extends this further.

What breaker and wire size do I need to connect a ResMed AirSense 11 CPAP (With Heated Humidifier & Tube) to the EcoFlow Delta Pro 3?

In the US, 65 W at 120 V is 0.5 A; applying the NEC 125% continuous-load rule gives 0.7 A, so use a 15 A breaker and 14 AWG copper for runs up to 25 ft (0.1% voltage drop). In 230 V markets the load draws 0.3 A, protected by a 6 A MCB on 1.5 mm² cable for runs up to 7.5 m. Receptacle: NEMA 5-15P (US) or BS 1363 13A / Schuko CEE 7/4 / AS/NZS 3112 10A (UK/EU/AU).

How long does it take to recharge the EcoFlow Delta Pro 3 with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 6.4 hrs of peak sun (1.4 days at 4.5 peak-sun-hours). At its maximum 2,600 W solar input it drops to 2.0 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the EcoFlow Delta Pro 3

All 50 loads on the EcoFlow Delta Pro 3 →

Other power stations for the ResMed AirSense 11 CPAP (With Heated Humidifier & Tube)

Compare every source for this load →

More Medical, IT & Critical Loads on the EcoFlow Delta Pro 3