Skip to content
GRIDSPEC
Verified Engineering Spec • NEC 2026 / UL 9540

Can the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank Run an Antminer S21 ASIC Hydro/Air Miner (240V PDU)?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank (10,240 Wh) paired with the Antminer S21 ASIC Hydro/Air Miner (240V PDU).

Configure your system

800 W
25 ft (7.6 m)
100%
Source outlets
Hardwired AC Distribution / L5-30R
Load connection
NEMA L6-30P / C19 PDU
Compatible 240V Alternative

Oukitel BP5000 Pro Max (5,000 W, 240V split-phase output) runs this load at 70% utilization.

As an Amazon Associate, we earn from qualifying purchases.

240V Split-Phase Required

Antminer S21 ASIC Hydro/Air Miner (240V PDU) needs a 240V split-phase circuit — the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank only outputs 120V.

Wattage is sufficient (3,500 W of 4,000 W), but the voltage is not.

Continuous load
88%
Runtime (no sun)
—
Needs 240V output
Solar recharge
16.0 hrs
3.6 sun-days at 800 W
Min. copper wire
12 AWG
0.6% drop @ 25 ft
Overcurrent device
20A Breaker
14.6A load × 1.25 = 18.2A
Live schematic & breaker sizing diagram 120/240V Split-Phase • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 B… 10,240 Wh • 4,000 W 9,000 W surge • 120V 88% load 20A OCPD 12 AWG Cu 14.6A @ 240V CONNECTED LOAD Antminer S21 ASIC Hydro/Air Miner (240V… 3,500 W running 3,800 W surge 240V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a Antminer S21 ASIC Hydro/Air Miner (240V PDU) on the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank

US/NA: 240V Split-Phase Required UK/EU/AU: Compatible · High Load 88% inverter utilization

When pairing the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank (10,240 Wh LiFePO4 capacity, 4,000 W continuous, 9,000 W surge) with a Antminer S21 ASIC Hydro/Air Miner (240V PDU) (3,500 W running, 3,800 W starting surge), the system operates at 88% of continuous inverter capacity on a 240 V North American circuit and 88% on a 230 V UK/EU/AU circuit. Our North American verdict is 240V Split-Phase Required, so the runtime figures below are theoretical battery-energy values only. Wiring the connection over a 25 ft run calls for a 20 A breaker and 12 AWG copper, terminated at a NEMA L6-30P / C19 PDU connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the Antminer S21 ASIC Hydro/Air Miner (240V PDU) loads the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank's inverter to 88% of its 4,000 W continuous rating and 42% of its 9,000 W surge rating. The blocking issue is voltage, not just wattage: the load requires a 240 V split-phase supply while this unit outputs 120 V only. The leanest compatible alternative in our database is the Oukitel BP5000 Pro Max.

CheckLoad requiresVictron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank providesUS/NAUK/EU/AU
Continuous output 3,500 W 4,000 W Pass Pass
Start-up surge 3,800 W 9,000 W Pass Pass
Voltage 240 V / 230 V 120 V / 230 V Fail Pass
Connection NEMA L6-30P / C19 PDU Hardwired AC Distribution / L5-30R UK/EU/AU: IEC 60309 16A Commando / Schuko 16A

Critical loads value uptime over raw power. At 3,500 W, this equipment is small relative to the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank's 4,000 W inverter, so the deciding factors are runtime, pure-sine output quality and switchover time. Most modern power stations offer UPS or EPS pass-through with a 10–30 ms transfer, which is fast enough for CPAP machines, routers and servers with active-PFC power supplies. For medical devices, always confirm with the device manufacturer and keep a secondary backup plan; for CPAP specifically, a DC adapter can extend runtime by 20–30% by skipping inverter losses.

The Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank is a marine and RV inverter-charger. Its strength is power quality and PowerAssist blending with shore or generator input rather than standalone 240V output.

Compatible alternative: the Oukitel BP5000 Pro Max with the Antminer S21 ASIC Hydro/Air Miner (240V PDU) report shows the full sizing for a unit that passes all three checks.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 10,240 Wh rating to about 8,704 Wh of deliverable AC energy (85% system efficiency). Duty cycle is the share of each hour the load actually draws its running power — thermostats, pressure switches and intermittent use all lower it.

Runtime (h) = (10,240 Wh × 0.85) ÷ (3,500 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 875 W 9.9 hrs 21.0 kWh
50% 1,750 W 5.0 hrs 42.0 kWh
65% 2,275 W 3.8 hrs 54.6 kWh
100% 3,500 W 2.5 hrs 84.0 kWh

Even at a 50% duty cycle the battery lasts 5.0 hrs, so plan on solar, grid or generator recharging for anything longer than an evening outage. Because the inverter cannot actually run this load in North American mode, treat these numbers as an energy-budget reference for a compatible inverter of the same capacity.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 3,500 W ÷ 240 V = 14.6 A, × 1.25 = 18.2 A, which rounds up to the next standard NEC 240.6 size of 20 A. The conductor must be protected by that breaker (75 °C ampacity at least 20 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (3,500 W ÷ 240 V) × 1.25 = 18.2 A → 20 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 20 A 12 AWG 0.59% Sized by ampacity
50 ft (15.2 m) 20 A 12 AWG 1.17% Sized by ampacity
75 ft (22.9 m) 20 A 12 AWG 1.76% Sized by ampacity
100 ft (30.5 m) 20 A 12 AWG 2.35% Sized by ampacity

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 15.2 A, so a 16 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 16 A 1.5 mm² 1.20%
15 m (49 ft) 16 A 1.5 mm² 2.40%
22.5 m (74 ft) 16 A 2.5 mm² 2.21%
30 m (98 ft) 16 A 2.5 mm² 2.94%

Because the current is modest, 12 AWG copper stays within the voltage-drop target all the way to 100 ft.

4. Solar Array Recharge Time Breakdown

The Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank accepts up to 5,000 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 32.0 hrs 7.1 −1,430 W
800 W 640 W 16.0 hrs 3.6 −1,110 W
1,600 W 1,280 W 8.0 hrs 1.8 −470 W
3,000 W 2,400 W 4.3 hrs 0.9 +650 W
5,000 W 4,000 W 2.6 hrs 0.6 +2,250 W

A typical 800 W portable array refills the battery in about 16.0 hrs of strong sun, while maxing out the 5,000 W input cuts that to 2.6 hrs. To fully offset the Antminer S21 ASIC Hydro/Air Miner (240V PDU) at a 50% duty cycle (1,750 W average) during daylight you need roughly 2,200 W of panels, which this unit can accept.

5. Frequently Asked Questions

Can the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank run a Antminer S21 ASIC Hydro/Air Miner (240V PDU)?

Not reliably in North America — our verdict is "240V Split-Phase Required". The load needs 240 V split-phase power and the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank outputs 120 V only. The Oukitel BP5000 Pro Max is a compatible alternative. In UK/EU/AU 230 V mode the verdict is "Compatible · High Load".

How long will the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank run a Antminer S21 ASIC Hydro/Air Miner (240V PDU)?

With 10,240 Wh of capacity and 85% inverter efficiency, expect about 2.5 hrs of continuous operation and 5.0 hrs at a 50% duty cycle — theoretical figures, since the inverter cannot actually sustain this load. Adding solar input during the day extends this further.

What breaker and wire size do I need to connect a Antminer S21 ASIC Hydro/Air Miner (240V PDU) to the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank?

In the US, 3,500 W at 240 V is 14.6 A; applying the NEC 125% continuous-load rule gives 18.2 A, so use a 20 A breaker and 12 AWG copper for runs up to 25 ft (0.6% voltage drop). In 230 V markets the load draws 15.2 A, protected by a 16 A MCB on 1.5 mm² cable for runs up to 7.5 m. Receptacle: NEMA L6-30P / C19 PDU (US) or IEC 60309 16A Commando / Schuko 16A (UK/EU/AU).

How long does it take to recharge the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 16.0 hrs of peak sun (3.6 days at 4.5 peak-sun-hours). At its maximum 5,000 W solar input it drops to 2.6 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank

All 50 loads on the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank →

Other power stations for the Antminer S21 ASIC Hydro/Air Miner (240V PDU)

Compare every source for this load →

More Medical, IT & Critical Loads on the Victron MultiPlus-II 48/5000 + 10kWh LiFePO4 Bank